• QUESTIONS? GIVE US A CALL! 1 (570) 823-6181

Navigate to the undefined homepage

You are here:Home >
SolaHD SDN1024100P

Sola SDN10-24-100P 240W 24V DIN S/P 115/230V IN

SolaHD SDN1024100P - Image 1 of 0
SolaHD SDN1024100P - Image 2 of 0
SolaHD SDN1024100P - Image 1 of 0
SolaHD SDN1024100P - Image 2 of 0
SolaHD SDN1024100P - Image 1 of 0
SolaHD SDN1024100P - Image 2 of 0

SolaHD SDN1024100P 240W 24V DIN S/P 115/230V IN

SolaHD
List Price: $659.48
$
You save $!
SDN10-24-100P
  • Manufacturer:: SolaHD
Product Code: SDN1024100P
UPC Code: 78347215321


The Next Generation SDN "P" Series
(Single and Three Phase Units, 60-960 Watts)
DIN Rail power supplies in this industry just got better. By adding a “P” to the single phase part number, you get better performance, additional applications and Power Factor Correction. These next generation power supplies have industry leading performance with a true industrial grade design and high quality that meets difficult industrial environmental conditions including high shock, vibration, and wide temperature ranges over the long life cycle of industrial equipment.

Features

  • Power Factor Correction
  • Auto Select 115/230 VAC, 50/60 Hz Input
  • Single Phase models meet SEMI F47 Sag Immunity
  • Class 1, Div 2 Hazardous Locations
  • Improved metal mounting clip
  • DC OK Signal
  • Adjustable Voltage
  • Industrial grade design.
    - 10oC to 60oC operation without derating. Indefinite short circuit,
    overvoltage and overtemperature protection.
    - Powers high inrush loads without shutdown or foldback.
  • - Rugged metal case and DIN connector.
  • SDN10-24-100P New Compact width (3.26”)
  • Parallel Capability standard on all units.
  • Broad range ( 2.5 A through 40 A) of product to fit almost any application.
  • Narrow width on rail for space critical applications.
  • 2.5-24-100P meets NEC Class 2.

    • User-friendly front panel.
      - Large, rugged, accessible, multiple connection screw terminations.
      - Easy installation.
    • High MTBF and reliability
    • Five year warranty.
    • Single and three phase inputs available.
    • Highly efficient >90% switching technology.

    EMC and
    Low Volt.
    Directive

    UL 508 Listed
    IND CONT. EQ.
    18 WM, E61379

    UL 60950
    E137632
    cUL/CSA-C2202
    No. 234-M90

    Applications

    • Industrial/Machine control
    • Vending Machines
    • Process control
    • Packaging Equipment
    • Material Handling
    • Amusement Park Equipment
    • Conveying Equipment
    • Semiconductor Fabrication Equipment
    • DeviceNetTM
    Accessories
    • Chassis Mount Bracket (SDNPMBRK2)

    Specifications (Single Phase)

    Description

    Catalog Number

    SDN 2.5-24-100P

    SDN 4-24-100PSDN 5-24-100PSDN 10-24-100PSDN 20-24-100P

    Input

    Nominal
    Voltage

    115/230 VAC user select (no manual required)

    -AC Range

    85-132/176-264 VAC

    -DC Range

    90-375 VDC

    210 - 375 VDC

    N/A

    -Frequency

    47 - 63 Hz, 400 Hz Possible

    Nominal Current1

    1.3 A. / 0.7 A

    2.6 A. / 1.4 A6 A / 2.8 A typical12 A/6 A
    -Inrush
    current max.
    typ. <25 Atyp. <20 Atyp. <40 A
    Efficiency
    (Losses2)

    >87.5% typ
    (8.6 W)

    >88% typ
    (13.1 W)
    >88% typ (16.4 W)>88% typ
    (32.7 W)
    >90% typ
    (48 W)

    Output

    Nominal Voltage

    24 VDC (22.5 - 28.5 VDC Adj.)

    -Tolerance

    <±2% overall(combination line, load, time and temperature related changes)

    -Ripple3

    < 50 mVpp

    Nominal Current

    2.5 A (60 W)

    4 A (100 W)

    5 A (120 W)

    10 A (240 W)

    20 A (480 W)

    -Peak Power4

    2x Nominal Current
    < 2 sec.

    4.2 A max

    6 A
    2x Nominal Current
    < 2 sec.

    12 A
    2x Nominal Current
    < 2 sec.

    2x Nominal Current
    < 2 sec.

    -Current
    Limit
    Fold Forward (Current rises, voltage drops to maintain
    constant power during overload up to max peak current)
    Holdup Time

    > 20 ms (Full load, 100 VAC Input @ Tamb = +25oC to 95% output voltage.

    Parallel Operation Single or Parallel use is selectable via Front Panel Jumper.

    General

    EMI
    -Emissions
    EN50081-1,-2 Class B EN55011, EN55022 Radiated and Conducted including Annex A.
    -Immunity EN50082-1, -2; EN61000-4-2 Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4 Level 4
    input and Level 3 output; EN61000-4-5 Isolation Class 4 (SDN8-5-24 is Class 3), EN61000-4-11; Transient
    resistance according to VDE 0160/W2 over entire load range.
    Approvals EN60950; EN50178; EN60204; UL508 Listed, cULus; UL1950, cRUus, SDN2.5 - Class 2 LPS;
    CE (LVD 73/23 & 93/68/EWG, EMC 89/336 & 93/68/EWG; Transient Handling VDE 0160/W2.
    SDN 8-5-24 is CE marked with SE>V<42 V only.
    Temperature Storage: -25oC...+85oC Operation. -10o-60oC full power with operation to 70oC possible with a linear
    derating to half power from 60oC to 70oC. The relative humidity is 95% maximum non condensing.
    Warranty

    5 years

    General
    Protections/
    Safety
    Protected against short-circuit, overload, open-circuit. Overvoltage protection (OVP) for output set >30.5 but < 33 VDC, Auto Recovery. Protection class I (IEC536), degree of protection: IP20 (VDE 0470, IEC 529) Safe low voltage:
    SELV (acc. EN60950).
    Status
    Indicators
    Green LED and DC OK signal (300 mA @ 60 VDC)

    Installation

    Fusing
    -Input Internally fused. External 10 A slow acting fusing for the input is recommended for SDN2.5, 4 5 and 10P
    models. A 16A slow acting fuse or time-delay circuit breaker is recommended for the SDN20 model.
    -Output Outputs are capable of providing high currents for short periods of time for inductive load startup or
    switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated.
    Continuous current overload allows for reliable fuse tripping.
    Mounting Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted
    (optional screw mounting set SDN-PMBRK2 required).
    Connections Input: IP20-rated screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors.
    16-12 AWG (0.5-4 mm2) for flexible conductors.
    Output: Two connectors per output, connector size range: 16-10 AWG (1.5-6 mm2) for solid conductors.
    Case Fully enclosed metal housing with fine ventilation grid to keep out small parts.
    -Free Space

    25 mm above/below
    25 mm left/right
    10 mm in front

    25 mm above/below
    25 mm left/right
    15 mm in front

    70 mm above/below
    25 mm left/right
    15 mm in front

    H x W x D
    (inches/mm)

    4.88 x 1.97 x 4.55
    (124 x 50 x 116)

    4.88 x 2.56 x 4.55
    (124 x 65 x 116)

    4.88 x 3.26 x 4.55
    (124 x 83 x 116)

    4.88 x 6.88 x 4.55
    (124 x 175 x 116)

    Weight (lbs/g)

    1 lb (460g)

    1.5 lb (620g)

    2.2 lbs (1100g)3 lbs (1520g)
    Notes:
    1. Input current ratings are conservatively specified with low input, line conditions, worst case efficiency and power factor.
    2. Losses are heat dissipation in watts at full load, nominal input line.
    3. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.
    4. All peak power is calculated at 24 Volt levels.
    5. SDN20-24-100 can be ordered until the SDN20-24-100P is available for shipment (September, 2003).

    Specifications(Three Phase)

    Description

    Catalog Number

    SDN 5-24-480

    SDN 10-24-480

    SDN 20-24-480CSDN 30-24-480SDN 40-24-480

    Input

    Nominal
    Voltage

    3Æ 380-480
    VAC Auto Range

    1Æ or 3Æ, 380 - 480 VAC1

    3Æ 380-480 VAC
    -AC Range

    340-576 VAC

    -DC Range 450 - 820 VDC
    -Frequency

    47 - 65 Hz

    Nominal Current20.5 A1 A1.5 A2.0 A3.0 A
    -Inrush currenttyp. < 18 Atyp. < 30 A
    Efficiency
    (Losses2)
    >90% typ (12 W)>90% typ (48 W)>90% typ (72 W)>90% typ (96 W)
    Power Factor
    Correction
    Units fulfill EN61000-3-2

    Output

    Nominal Voltage

    24-28 VDC Adj. (22.3 - 28.5 VDC adj.)

    -Tolerance

    <±2% overall (combination line. load, time and temperature related changes)

    -Ripple4< 50 mVpp
    Nominal Current

    5 A (120 W)

    10 A (240 W)

    20 A (480 W)

    30 A (720 W)

    40 A (960 W)
    -Peak Current

    6 A
    2x Nominal Current
    < 2 sec.

    12 A
    2x Nominal Current
    < 2 sec.

    25 A
    2x Nominal Current
    < 2 sec.

    35 A
    1.5 x Nominal Current
    < 2 sec.

    45 A
    2x Nominal Current
    < 2 sec.

    -Current
    Limit

    Fold Forward
    (Current rises, voltage drops to maintain constant power during overload up to max peak current)

    Holdup Time

    >20 ms

    Parallel
    Operation
    The SDN20/30 may be passively paralleled by selecting the "P" position of the jumper on the unit.
    The SDN40 contains active current balancing.

    General

    EMI
    -Emissions

    -Immunity


    EN50081-1,-2 Class B EN55011, EN55022 Radiated and Conducted including Annex A.
    EN50082-1, -2; EN61000-4-2 Level 4, EN61000-4-3 Level 3; EN61000-4-6 Level 3; EN61000-4-4 Level 4
    input and Level 3 output; EN61000-4-5 Isolation Class 4, EN61000-4-11; Transient resistance according
    to VDE 0160/W2 over entire load range.
    Approvals CB Scheme, EN60950; EN50178; EN60204; UL508 Listed, cULus; UL60950, cRUus, CE (LVD 73/23 &
    93/68/EEC). EN61000-3-2, IEC 60079-15 (Class 1, Zone 2 hazardous location, Groups IIA, IIB, IIC
    w/T3 temp class up to 60°C Ambient.
    Temperature Storage: -25oC...+85oC Operation. -10o-60oC full power with operation to 70oC possible with a linear
    derating to half power from 60oC to 70oC. (Convection cooling, no forced air required). Operation up to
    50% load permissable with sideways or front side up mounting orientation. The relative humidity is less
    <90% RH, noncondensing; IEC 68-2-2, 68-2-3.
    Warranty

    5 years

    General
    Protection/
    Safety
    Protected against continuous short-circuit, overload, open-circuit. Protection class 1 (IEC536),
    degree of protection IP20 (IEC529). Safe low voltage: SELV (acc. EN60950).
    Status Indicators Green LED on, when Vout = 18V or greater.

    Installation

    Fusing
    -Input Internally fused.
    -Output Outputs are capable of providing high currents for short periods of time for inductive load startup or
    switching. Fusing may be required for wire/loads if 2x Nominal O/P current rating cannot be tolerated.
    Continuous current overload allows for reliable fuse tripping.
    Mounting Simple snap-on system for DIN Rail TS35/7.5 or TS35/15 or chassis-mounted
    (optional screw mounting set SDN-PMBRK2 required).
    ConnectionsInput: IP20 related screw terminals, connector size range: 16-10 AWG (1.5-6 mm2) for solid
    conductors. 16-12 AWG (0.5-4 mm2) for flexible conductors.
    Output: two connectors per output, connector size range: 16-10 AWG (1.5 - 6 mm2) for solid connectors.
    Case Fully enclosed metal housing with fine ventilation grid to keep out small parts.
    -Free Space

    25 mm above/below
    25 mm left/right
    15 mm in front

    70 mm above/below
    25 mm left/right
    15 mm in front

    H x W x D
    (inches/mm)

    4.88 x 2.91 x 4.55
    (124 x 73 x 116)

    4.88 x 3.5 x 4.55
    (124 x 89 x 116)

    4.88 x 5.9 x 4.55
    (124 x 150 x 116)

    4.88 x 9.72 x 4.55
    (125 x 247 x 116)

    4.88 x 11.1 x 4.55
    (125 x 282 x 116)

    Weight (lbs/g)

    1.7 lbs (730g)

    2.16 lbs (980g)

    3.97 lbs (1800g)

    4 lbs (2000g)6.6 lbs (3300g)
    Notes:
    1. For the SDN20-24-480C, single phase input is permissible but output is derated to 75% (15 Amps @ 24 VDC).
    2. Input current ratings are conservatively specified with low input, worst case efficiency values and power factor.
    3. Losses are heat dissipation in watts at full load, nominal input line.
    4. Ripple/noise is stated as typical values when measured with a 20 MHz, bandwidth scope and 50 Ohm resistor.