The
Extech PQ3350-1 is a 3-Phase Power & Harmonics Analyzer capable of up to 52,428 single phase readings or 17,476 3-phase readings. It includes a large backlighting LCD displays up to 35 parameters in one screen, and allows for the simultaneous display of harmonics and waveform. For single and 3-phase/3-wire or 3-phase/4-wire systems. Complete with 3 flexible current clamps, 4 voltage leads with alligator clips and retractable plunger clips, 8 AA batteries, universal AC adaptor, software, USB interface cable, and case.
GENERAL SPECIFICATIONS- AC Current - 1200A
- AC Current Basic Accuracy - ±(0.5% of reading + 5 digits)
- AC Voltage - 600V
- AC Voltage Basic Accuracy - ±(0.5% of reading + 5 digits)
- Active Power - 9.999MW
- Active Power Basic Accuracy - ±(1% of reading + 8 digits)
- Active Power Energy - 0mWh to 999,999kWh
- Apparent Power - 9999kVA
- Apparent Power Basic Accuracy - VA=Vrms x Arms
- Crest Factor - 1.00 to 99.99
- Crest Factor Basic Accuracy - ±(5% of reading + 30 digits)
- Frequency - 45-65Hz
- Frequency Basic Accuracy - 0.1Hz
- Harmonics - 1 to 99
- Harmonics Basic Accuracy - ±2%
- Memory - 52428 records (single phase); 17476 records (3 phase)
- Peak AC Current Basic Accuracy - ±(5% of reading + 30 digits)
- Peak AC Voltage Basic Accuracy - ±(5% of reading + 30 digits)
- Phase -180.0° to 0° to +180.0°
- Phase Basic Accuracy - ±1°
- Power Factor - 0.0 to +1.00
- Power Factor Basic Accuracy - ±(1.5%° of reading ± 8 digits)
- Reactive Power - 9999kVAR
- Reactive Power Basic Accuracy - VAR= sqr (VA² -W² )
- Reactive Power Energy - 0.0kVARh to 1000MWh
- True RMS - Yes
ADDITIONAL DETAILS
- Certifications - CE
- Dimensions - 10.1 × 6.1 × 2.3" (257 × 155 × 57mm)
- Power - 8 × AA (1.5V) batteries
- Safety Category - CATIII - 600V
- Warranty2 years
- Weight - 2.5 lbs (1160g)
OTHER