Presentation | Highly efficient, easy-to-deploy 80kW, 400V 3-phase uninterruptible power supply (UPS) that brings best-in-class power protection to edge, small and medium data centers, as well as to critical infrastructure in commercial and industrial applications. Compact design, high-density technology and modular architecture keep total cost of ownership low and operational efficiency at the highest levels. Galaxy VS reduces your energy losses by up to 66% with eConversion mode – reaching up to 99% efficiency levels and delivering more energy savings than even our industry-leading 97% efficiency in double conversion mode. The UPS is EcoStruxure connected to give you peace of mind with cloud-based remote monitoring and management via your smartphone. Includes 5x8 start-up service. |
---|---|
Lead time | Usually Ships within 2 Weeks |
Main Input Voltage | 400 V 3 phase |
---|---|
Other Input Voltage | 380 V 415 V |
Main Output Voltage | 400 V 3 phase |
Other Output Voltage | 380 V 415 V |
Kw Rating | 80 kW |
Rated power in VA | 80 kVA |
Output connector type | Hard Wire 5-wire (3PH + N + G) 1 |
battery type | External battery system Li-Ion (Lithium Ion) VRLA |
Provided equipment | Dust filter Installation guide Integrated network management Power modules ship installed Start-Up Service Top and bottom cable entry |
battery voltage | 384-576VDC |
---|---|
End of Discharge Battery Voltage | 307 V DC |
End of Discharge Maximum Battery Current | 217 A |
Battery power in VAH | 0 VAh runtime |
Extendable Run Time | 0 |
Bypass Voltage Tolerance | +/- 10 % |
---|---|
Max Bypass Input Current | 129 A |
Redundant | No |
color | White |
---|---|
Height | 58.46 in (148.5 cm) |
Width | 20.51 in (52.1 cm) |
Depth | 33.35 in (84.7 cm) |
Net Weight | 551.16 lb(US) (250 kg) |
USB compatible | No |
Input Frequency | 40 - 70 Hz |
---|---|
Number of input connectors | 1 Hard Wire 3-wire (3PH + G) 1 Hard Wire 5-wire (3PH + N + G) |
Efficiency at full load | 340...460 V 400 V |
Maximum Input Current per Phase | 148 A |
Maximum Short Circuit Withstand (Icw) | 65 kA |
Input Total Harmonic Distortion | Less than 3% for full load |
Load power factor | From 0.7 leading to 0.7 lagging without any derating |
Input Power Factor at Full Load | 0.99 |
Max Configurable Power (Watts) | 80 kW |
---|---|
Harmonic distortion | Less than 3% |
Output Frequency (sync to mains) | 50 Hz sync to mains 60 Hz sync to mains 60 Hz +/- 0.1 % for 60 Hz nominal not synced 50 Hz +/- 0.1 % for 50 Hz nominal not synced |
Crest factor | 2.5 |
Waveform Type | Sine wave |
Output voltage tolerance | +/-1% after 50ms |
Output Voltage THD | < 1% linear load and < 3% non-linear load |
Overload Operation | 10 minutes @ 125% and 60 seconds @ 150% |
bypass type | Built-in Static Bypass |
Maximum configurable power in VA | 80 kVA |
Standards | CSA C22.2 No 107.3 EN/IEC 62040-1 EN/IEC 62040-2 EN/IEC 62040-3 FCC Part 15 class A IEC 60721-4-2 Level 2M2 UL 1778 5th edition |
---|
Ambient air temperature for operation | 32…104 °F (0…40 °C) |
---|---|
Relative Humidity | 0…95 % non-condensing |
Operating altitude | 0...3281 ft |
Ambient Air Temperature for Storage | -13…131 °F (-25…55 °C) |
Storage Relative Humidity | 10…80 % non-condensing |
Storage altitude | 0…50000 ft (0.00…15240.00 m) |
Acoustic level | 65 dBA |
Heat dissipation | 7449 Btu/h |
IP degree of protection | IP21 |
Free slots | 1 |
---|---|
control panel | Touch Screen LCD User Interface |
GTIN | 731304342823 |
---|
Unit Type of Package 1 | PCE |
---|---|
Number of Units in Package 1 | 1 |
Package 1 Height | 66.14 in (168 cm) |
Package 1 Width | 38.98 in (99 cm) |
Package 1 Length | 25.20 in (64 cm) |
Package 1 Weight | 606.27 lb(US) (275 kg) |
Warranty | 1 year on-site repair or replace with factory authorized Start-Up |
---|